SKM Heat Sensing Cable System

The SKM Heat Sensing Cable System provides early warning of an impending fire by detecting overheating in cable ducts, road tunnels, escalators, lift shafts, conveyer belts and similar difficult to monitor environments.

The system uses 'Firesense' analogue heat sensing cable and the SKM-03 or SKM-95 controllers plus an end of line terminal box. The sensor cable is a specially constructed coaxial cable.

The System works with Conventional fire systems using SKM-03 & SKM-03UK Controllers, and Analogue Addressable Apollo XP95 Systems using the SKM-95 Controller. The SKM Heat Sensing Cable System is EN54 approved.

When the cable is heated there is a corresponding change in the electrical characteristics of the cable. This change is monitored by the controller which when sufficient causes an alarm. The controller constantly monitors for open and short circuit faults in the cable.

SKM Heat Sensing Cable Controller

 

Firesense cable may be physically heat tested any number of times by the application of heat in order to test the system, however if it is destroyed by overheating or fire, the damaged section must be replaced.

Key Features

  • Easy and economical to install;
  • User friendly;
  • Controller will monitor up to 300 m of sensor cable (dependant on ambient temperature);
  • Temperature increases are detected in proportion to the length of cable heated;
  • The sensor cable is resistant to corrosion & moisture;
  • VdS approved;
  • SKM-03 for use on conventional fire panels;
  • Loop powered SKM-95 controller for use on addressable fire panels (XP95 Series protocol);
  • Cable can be reset after use.

 

Controller Specifications

 
 SKM-95SKM-03VdS & SKM-03UK
Supply VoltageLoop powered24Vdc
Idle current consumption< 2 mA28 mA
Alarm current3.2 mA58 mA
Isolator voltage< 14 VNot applicable
Address protocolXP95 SeriesN/A
ResponseEN54 compliantSKM-03VdS: EN54 compliant
SKM-03UK: Alarm raised when
1m of cable is heated to 60°C
'FIRE' Relay contactN/ANO/NC Relay contacts
'FAULT' Relay contactN/ANO/NC Relay contacts
Dimensions: W/H/D105/105/65 mm105/105/65 mm
Weight270 g270 g
System Healthy LED IndicatorGreenGreen
'FIRE' LED IndicatorRedRed
Colour of housing: grey, RAL 9002grey, RAL 9002
IP Rating :IP65IP65

 

SKM-03, SKM-03UK & SKM-95 CONTROLLERS

SKM Controllers, Dimensions 1SKM Controllers, Dimensions 2

 

END OF LINE UNIT

End of Line Unit Dimensions

For details on the Firesense Cable and its specifications, please see the Firesense 2000 Heat Sensing Cable datasheet.